This Static Voltage Regulator usually works the first time with no problems after installation. But after 25 years of experience I like to tell you about the most common problem I had.
- The customer says that the output voltage of the generator is on haft of normal voltage. Specially if the generator is wired to work at 480 Volts output. The problem here is that the INPUT sensing wires of the AVR is not INSTALLED on the First STAR of the generator but on the output power lines. SOLUTION install them on the FIRST START.
- The customer says that he has no power at all coming out of the generator. The SOLUTION is to REVERSE the wires on the slip rings.
- Another problem is that the generator has no Residual voltage to start the build-up process. The SOLUTION is to FLASH the Generator.
- If you need help call me at 1-800-541-7677. We can work it out on the phone.
|