Voltage Build Up: When residual voltage is larger than 5V 25Hz, the voltage will build up automatically.
Exciter field Resistance: minimum 8 Ohms, 10 Ohms at 125V output.
External Voltage Adjustment: When fitted with 1000 Ohms, voltage adjust range +-10% Variable Resister rated minimum rate is 0.5W.
Under Frequency Protection: 60Hz. If the generator is lower than 55 Hz, this regulator will show down immediately. (refer to Fig2). 50Hz. If the generator is lower than 45 Hz, this regulator will shut down immediately. (Refer to Fig2)
Usage Temperature: -10C ~ 60C
Storage Temperature: -60C ~85C
Size: 150 mmL * 100 mmW * 63 mmH
Weight: 16 oz / 475 Grams
Voltage soft start: Build in voltage soft start function.