:: How to assemble ATS::
ATS3BC0600/0800
ATS4BC0600/0800
 Automatic Transfer Switch 600 & 800Amp
  • MCCB Type Automatic Transfer Switch
  • Rated Current 500~800Amp
  • Voltage 100~600VAC

Brochure
Features
  • Modularized ATS Design
  • Superior Serviceability & Simple Maintenance
  • ATS-01* Controller-Provides Monitoring & Protection with Built-in 168HR Exerciser Timer
  • TSP-01* Voltage Transformer Module-Change Voltage Easily by Plug-In Connectors
  • BTS*-Transfer Switch Built with High Short Circuit Breaking Capacity & OCPD**
  • All Modules Connected by Harness with High Voltage Withstand Plug-In Connectors
  • Complies with IEC 60947-6 Requirements***

    *KUTAI modularized ATS is combined with enclosure, ATS-01, TSP-01 & BTS. For more details, please check the brochure & manual of each item.

    ** OCPD:
    Over Current Protection Device

    *** IEC60947-6 Class CB:
    ATS provided with over current releases and the main contacts of which are capable of making and are intended for breaking short circuit currents.

    *** IEC60947-6 Utilization Category AC-33A:
    1. Frequent operations
    2. Motor loads or mixed loads including motors, resistive loads and up to 30% incandescent lamp
ATS Rated Operating Current & AC Rated Breaking Capacity
ATS Type Pole Rated Current (A)
Ambient Temperature 40°C
AC Rated Breaking Capacity
Sym r.m.s(KA)   IEC 60947-2 Icu/Ics
240V 380V 415V 440V 500V 690V
ATS3BC0600 3P 500 600 35 25 25 20 18 --
ATS4BC0600 4P 500 600 50 45 35 30 25 16
ATS3BC0800 3P 700 800 50 45 35 30 25 16
ATS4BC0800 4P 700 800 85 65 50 50 35 20

*For special high breaking capacity requirements, please contact us.
Mechanical Specifications

Enclosure P/N. CA-225 CA-400
H 1800 1800
W 820 912
D 640 640
Thickness 2.0 2.0
Fixed Type Floor Floor
MCCB Capacity 3P 500~1600 A 4P 500~1600 A
Wire Portal Dimensions OB* OB*
Outdoor Enclosures Please contact us if rain-proof (for outdoor use) enclosure is needed.