| ATS2PC0125 Residential Automatic Transfer Switch |
- Double Throw Type ATS
- Single Phase, 2P 100 Amp / 250 VAC
|


|
| Features |
- Modular design for installation next to switch or on the door
- Electrically or Manually Operated, Mechanically Held Contacts
- Adjustable Time Delay on Neutral
- Compact Size with User-Friendly Status LED Display
- Monitor normal source over and under voltages
- Built-in 7-Days With/Without Load Exerciser
- Made with UL 94V-0 plastic
- Build-in Neutral lug module
- Designed for cell-phone industry or home ATS applications
|
|
| TS125 Specifications |
| Rated Voltage |
120/240 VAC |
| Rated Current |
125 A |
| Rated Frequency |
50/60 Hz |
| Transfer |
Double Throw Type |
| Operating Current |
2.0A @ 220V |
| Poles |
2P |
| Rated Short-Time Current |
3.0 KA/1 Sec @ 250 VAC |
| Short Circuit Peak Value |
7.5 KA |
| Utilization Category |
AC-33A |
| Life |
> 6000 Times/With Load |
| Rated Operating Voltage |
TCS2P125-11 / 90 ~ 140VAC
TCS2P125-22 /180 ~ 270VAC |
| Class |
PC |
|
* IEC60947-6 Utilization Category AC-33A:
1. Frequent operations
2. Motor loads or mixed loads including motors, resistive loads and up to 30% incandescent lamp |
| TC125 Specifications |
| Over Volt Setting |
270/150VAC (Un-adjustable) |
| Over Volt Reset |
260/140VAC |
| Under Volt Setting |
170/80VAC (Un-adjustable) |
| Under Volt Reset |
180/90VAC |
| Adjustable Time Delay |
TDEN 0 ~ 30 Sec ±10%
TDNE 0 ~ 30 Sec ±10%
TDEC 0 ~ 120 Sec ±10%
TDES 0 ~ 90 Sec ±10%
TDOFF 0 ~ 18 Sec ±10% |
| Normal ON Capacity |
7A @ 250 VAC Max |
| Standby ON Capacity |
7A @ 250 VAC Max |
| Remote Start Capacity |
6A @ 277 VAC / 6A @ 28 VDC Max |
| Power Consumption |
< 1W |
|
|
| Mechanical Specifications |

| General Specifications |
| Operation Temperature |
-10~70°C |
| Humidity |
9.0KG ±2% |
| Dimensions |
H x W x D = 370.0 x 300.0 x 159.0 mm |
|
|